ABL6TS16G

Main

[TAG[ hide ]]
range of product Phaseo Optimum  
product or component type Safety and isolation transformer  
rated power in VA 160 VA  
input voltage 230 V AC single phase, terminal(s): N-L1
400 V AC phase to phase, terminal(s): L1-L2
 
output voltage 115 V AC  
secondary winding Single  
protective cover Without  
ambient air temperature for operation -20...50 °C  
 
Complementary

[TAG[ hide ]]
input voltage limits 207...253 V
360...440 V
 
network frequency limits 47...63 Hz  
input voltage tolerance +/- 15 V  
efficiency 88 %  
power dissipation in W 21.8 W  
output sustained overvoltage 6 % (no load, hot state)  
voltage drop at rated load 0.7 %  
no load losses 9.1 W  
short-circuit voltage 0,0665  
output protection type Against overload, protection technology: external
Against overvoltage, protection technology: external
Against short-circuits, protection technology: external
 
connections - terminals Screw type terminals for input connection, connection capacity: 5 x 4 mm² AWG 11
Screw type terminals for input ground connection, connection capacity: 1 x 4 mm² AWG 11
Screw type terminals for output connection, connection capacity: 2 x 4 mm² AWG 11
 
marking CE  
fixing mode By 4 screws, screw(s) Ø = 5.8 mm on horizontal panel with derating to 90 %
By 4 screws, screw(s) Ø = 5.8 mm on vertical panel, operating position: horizontal
By 4 screws, screw(s) Ø = 5.8 mm on vertical panel, operating position: vertical
 
operating altitude 3000 m  
electrical insulation class Class B  
product weight 3.2 kg  
 
Environment

[TAG[ hide ]]
product certifications UR
EAC
 
standards UL 506  
IP degree of protection IP20  
environmental characteristic EMC conforming to EN 62041
Safety conforming to EN 61558-1
Safety conforming to EN 61558-2-6
 
protective treatment TC  
ambient air temperature for storage -40...80 °C  
overvoltage category Class I conforming to VDE 0106-1  
dielectric strength 2000 V between winding and ground
4000 V between primary and secondary