ASI20MT2I1OTE

Main

[TAG[ hide ]]
range of product Advantys  
product or component type Modular interface  
addressing Extended A/B  
number of addresses 0...62  
discrete input number 2  
discrete output number 1 2 A triac  
supply Via AS-Interface line for sensor
Via external supply for actuactor
 
actuator sensor interface profile [AS-i] S3.A.7.0  
 
Complementary

[TAG[ hide ]]
range compatibility AS-Interface cabling system  
AS-Interface compatibility V2.1  
[Us] rated supply voltage 26.5...31.6 V DC for AS-Interface line  
maximum sensor supply current 170 mA  
current consumption 15 mA on no load for AS-Interface line
<= 40 mA on inputs/outputs on and sensor not energised
 
input compatibility 2 or 3-wire PNP conforming to IEC 61131-2 Type 2  
voltage state 1 guaranteed > 11 V (sensor side)  
current state 1 guaranteed >= 6 mA (sensor side)  
voltage state 0 guaranteed < 5 V (sensor side)  
current state 0 guaranteed <= 2 mA (sensor side)  
discrete output voltage 24...250 V AC conforming to IEC 60947-5-1  
drop-out voltage <= 3 V at Ith (actuator side)  
thermal current per channel 2 A (actuator side)  
thermal current per common 2 A (actuator side)  
[Ie] rated operational current 2 A, operating rate = 6 cyc/mn AC-12 conforming to IEC 60947-5-1 (actuator side)  
minimum output current 8 mA  
overcurrent protection Without  
switching time 10 ms for OFF to ON (actuator side)
10 ms for ON to OFF (actuator side)
 
output fallback position State 0 if watchdog tripped  
parameter bits Not used  
overvoltage category II conforming to EN/IEC 60664-1  
electrical connection Removable terminal block (actuator side)
Removable terminal block (AS-Interface line)
Removable terminal block (sensor side)
 
fixing mode By 2 screws, Ø 3 mm on panel
Clip-on on 35 mm symmetrical DIN rail, operating position: horizontal
 
housing material Polycarbonate  
flame retardance V0 conforming to UL 94  
local signalling 1 LED green, function: AS-Interface power on
1 LED green, function: auxiliary supply on
1 LED red, function: no data exchange on AS-Interface (on steady), peripheral fault (flashing)
3 LEDs yellow, function: input/output status
 
product weight 0.09 kg  
 
Environment

[TAG[ hide ]]
product certifications AS-Interface No 52801
CSA
UL
 
ambient air temperature for operation -20...60 °C  
ambient air temperature for storage -40...85 °C  
IP degree of protection IP20 conforming to EN/IEC 60529  
shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27  
vibration resistance +/-1 mm (f = 2...13.2 Hz)
1 gn (f = 13.2...100 Hz)
 
resistance to electrostatic discharge 6 kV conforming to EN/IEC 61000-4-2  
resistance to radiated fields 10 V/m conforming to EN/IEC 61000-4-3  
resistance to fast transients 2 kV conforming to EN/IEC 61000-4-4  
dielectric test voltage 3.75 kV between AS-Interface line and triac output conforming to EN/IEC 60364-4-41  
pollution degree 2 conforming to EN/IEC 60664-1