ASIABLB3004

Main

[TAG[ hide ]]
range of product Phaseo AS-Interface  
product or component type Power supply  
power supply type Regulated switch mode  
output voltage 30 V DC for AS-Interface line  
rated power in W 144 W  
input voltage 100...240 V AC phase to phase, terminal(s): L1-L2
100...240 V AC single phase, terminal(s): N-L1
 
power supply output current 4.8 A  
operating position Vertical  
 
Complementary

[TAG[ hide ]]
input voltage limits 85...264 V  
network frequency limits 47...63 Hz  
input voltage tolerance - 15...10 %  
inrush current < 30 A  
cos phi 0.65  
efficiency > 83 % at 30 V  
power dissipation in W 29.5 W at 30 V  
current consumption 1 A  
input protection type Integrated fuse (not interchangeable)  
line and load regulation 3 %  
residual ripple 300 mV  
holding time >= 10 ms  
output protection type , protection technology: 1.1 x In
, protection technology: tripping if U > 1.2 x Un
, protection technology: automatic reset
, protection technology: tripping if U < 0.95 x Un
 
connections - terminals Screw type terminals for AS-Interface line, connection capacity: 4 x 2.5 mm², number of terminals = 4, cable cross section = 2.5 mm² AWG 14
Screw type terminals for input connection, connection capacity: 2 x 2.5 mm², number of terminals = 2, cable cross section = 2.5 mm² AWG 14
Screw type terminals for input ground connection, connection capacity: 1 x 2.5 mm², number of terminals = 1, cable cross section = 2.5 mm² AWG 14
Screw type terminals for output ground connection, connection capacity: 2 x 2.5 mm², number of terminals = 2, cable cross section = 2.5 mm² AWG 14
 
mounting support 35 mm symmetrical DIN rail
75 mm symmetrical DIN rail
 
operating altitude 2000 m  
name of test Conducted/radiated emissions conforming to EN 55022 Class B
Electrostatic discharges conforming to EN/IEC 61000-4-2
Emission conforming to EN 61000-6-3
Induced electromagnetic field conforming to EN/IEC 61000-4-6
Primary outage conforming to IEC 61000-4-11
Radiated electromagnetic field conforming to EN/IEC 61000-4-3
Rapid transient conforming to IEC 61000-4-4 level 3
Vibration conforming to EN/IEC 61131-2
 
meantime between failure [MTBF] > 100000 h at 40 °C  
status LED 1 LED green for output voltage
1 LED orange for input voltage
 
product weight 1.3 kg  
 
Environment

[TAG[ hide ]]
product certifications CSA 22-2 No 950
TUV 60950-1
UL 508
 
environmental characteristic EMC conforming to EN 50081-1
EMC conforming to EN 55022 Class B
EMC conforming to EN/IEC 61000-6-2
Safety conforming to EN 60950-1
 
IP degree of protection IP20 conforming to EN/IEC 60529  
ambient air temperature for operation 50...60 °C with derating factor
0...50 °C without derating factor
 
ambient air temperature for storage -25...70 °C  
relative humidity 0...95 % without condensation or dripping water  
dielectric strength 3000 V between input and ground
3000 V between input and output
500 V between output and ground
500 V between outputs