ZCD26
limit switch body ZCD - compact - 1NC+1NO - slow-break
Main

Hide
range of product OsiSense XC  
series name Standard compact  
product or component type Limit switch body  
device short name ZCD  
design Compact  
body type Fixed  
associated head ZCE01
ZCE02
ZCE05
ZCE06
ZCE07
ZCE08
ZCE10
ZCE11
ZCE13
ZCE14
ZCE21
ZCE24
ZCE27
ZCE28
ZCE29
ZCE62
ZCE63
ZCE64
ZCE65
ZCE66
ZCE67
ZCEH0
ZCEH2
 
body material Zamak  
number of poles 2  
contacts type and composition 1 NC + 1 NO  
contact operation Slow-break, make before break  
 
Complementary

Hide
associated connection component ZCDEF12
ZCDEG11
ZCDEG13
ZCDEN12
ZCDEP16
ZCDEP20
 
electrical connection Screw-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm²  
contacts insulation form Zb  
contacts material Silver plated contacts  
positive opening With  
minimum actuation speed 6 m/s  
contact code designation B300, AC-15 (Ue = 240 V, Ie = 1.5 A) conforming to EN/IEC 60947-5-1 appendix A
R300, DC-13 (Ue = 250 V, Ie = 0.1 A) conforming to EN/IEC 60947-5-1 appendix A
 
[Ui] rated insulation voltage 500 V degree of pollution 3 conforming to IEC 60947-1
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
 
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60664
6 kV conforming to IEC 60947-1
 
short-circuit protection 10 A by gG cartridge fuse  
electrical durability 5000000 cycles, DC-13 120 V, 7 W, operating rate: < 60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 24 V, 13 W, operating rate: < 60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 48 V, 9 W, operating rate: < 60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
 
width 31 mm  
height 65 mm  
depth 30 mm  
product weight 0.14 kg  
 
Environment

Hide
product compatibility XCKD  
ambient air temperature for operation -25...70 °C  
ambient air temperature for storage -40...70 °C  
 
Offer Sustainability

Hide
Sustainable offer status Green Premium product  
RoHS (date code: YYWW) Compliant - since 1136 - Schneider Electric declaration of conformity  
REACh Reference not containing SVHC above the threshold  
Product end of life instructions Need no specific recycling operations